Neon sign safety and regulations

Installed correctly, a glass neon sign is no more dangerous than other electrical equipment. This guide summarises the main UK and European standards and the points installers ask us about most. It is a summary only: always work to the current editions of the standards and BS 7671, and use a competent electrician for the mains supply.

The main standards

  • BS EN 50107-1: signs and luminous discharge tube installations operating from a no-load output voltage over 1kV but not over 10kV. Covers design, construction and installation.
  • BS EN 50107-2: earth leakage and open circuit protective devices for those installations.
  • BS 7671 (IET Wiring Regulations): the mains installation, including the requirement for a firefighter's switch.
  • BS 559: design, construction and installation of signs.

SIET transformers conform to EN 61050 and EN 50107.

Open circuit and earth leakage protection

A high voltage neon installation needs protection that cuts the output if a tube breaks (open circuit) or current leaks to earth.

  • Hansen convertors over 990V have earth leakage and open circuit protection built in.
  • All SIET transformers include an earth leakage trip fitted internally. If you dim or flash a SIET transformer, use external protection: call us first.
  • 990V (low voltage output) convertors are below the 1kV threshold of EN 50107-1.

Signs within arm's reach

EN 50107 defines arm's reach as 1.25m sideways and below any surface a person can stand on, and 2.5m above it. Within this zone:

  • Tubes fully enclosed in a case (for example acrylic) need no extra protection against contact.
  • If the tubes can be touched, the sign needs a mechanically protective enclosure to at least IP2X and open circuit protection.
  • Electrode connections must be protected by silicone covers, fixed so a tool is needed to remove them, or housed behind a tray.
  • Exposed metal parts must be earthed.

Firefighter's switch

BS 7671 requires a firefighter's switch for exterior installations, and for interior discharge lighting installations that run unattended, operating above low voltage. Covered markets, arcades and shopping malls count as exterior. In outline:

  • Exterior signs: the switch is outside the building, next to the sign, or with a notice by the sign saying where it is.
  • Interior signs: the switch is at the main entrance, or another position agreed with the fire authority.
  • It must be conspicuous, reachable by firefighters, and normally no more than 2.75m above the ground.
  • It is coloured red, marked FIREFIGHTER'S SWITCH, with the OFF position at the top.
  • Separate switches for interior and exterior installations, each marked with what it controls.

Signs on 990V convertors are low voltage and don't need one. Check the current edition of BS 7671 and ask the local fire authority if in doubt.

Good installation practice

  • Keep HT cables as short as possible and mount the power supply close to the tubes.
  • Use HT cable rated for the voltage, and don't run it inside metal conduit or bundled with other cables.
  • Don't connect the tubes of several letters to one convertor.
  • Support tubes on proper tube supports so no weight is on the electrodes.
  • Outdoors, use power supplies rated for outdoor use. Hansen 5kV and 8kV convertors are indoor only.
  • Label the sign with a high voltage warning.

Common questions

Do neon signs get hot, explode or use a lot of power? See our neon facts page and downloadable PDF.

Questions about a specific job? Call 01892 783 900.